Voltage Drop Calculator
Calculate how much voltage is lost over a wire run and find the minimum AWG to stay within your voltage-drop target. Uses the NEC standard formula (K × I × L / CM). Your inputs never leave your browser.
Inputs
Frequently Asked Questions
Vd = phaseFactor × K × I × L / CM — where phaseFactor is 2 for single-phase or √3 for three-phase, K is the resistivity constant (12.9 for copper, 21.2 for aluminum in ohm-cmil/ft), I is the design current in amps, L is the one-way run length in feet, and CM is the conductor cross-sectional area in circular mils. This formula is standard in NEC handbooks and Ugly's Electrical Reference.
NEC 210.19(A) informational note recommends limiting branch-circuit voltage drop to 3%, and NEC 215.2(A) informational note recommends 3% on feeder circuits, for a combined maximum of 5% from service to outlet. 3% is not an NEC mandate, but it is the widely accepted engineering benchmark.
K ≈ 12.9 ohm-cmil/ft for copper and ≈ 21.2 ohm-cmil/ft for aluminum at 75°C. These values are derived from the resistivity of each material and are widely published in NEC training materials, Ugly's Electrical Reference, and NECA/IBEW references.
Enter the one-way distance from the panel to the load — the formula accounts for the full conductor path. For single-phase, the factor of 2 represents the round trip (outgoing plus return conductor). For balanced three-phase, the factor of √3 (≈1.732) is the geometric line-to-line factor for a three-phase system, not a round-trip conductor count; in either case you still enter only the one-way run length.
Voltage drop is proportional to run length. On short circuits (under 50 ft at typical household loads), ampacity is usually the binding constraint. On long runs — outdoor lighting, subpanels, EV chargers at the far end of a property — voltage drop becomes the larger wire size driver.
← Back to full Wire Size Calculator • EV Charger Wire Size Calculator →